How does it work?
When power is supplied to the unit, the water fill valve opens and it enters the tank. Once the level reaches the low-water switch, the heating elements are energized (assuming there's a call for steam output). The unit continues to fill until the high-water switch is reached. The humidifier then produces steam in response to the humidistat's input signal. Periodic tank drainage is based on active time of the heating elements, but may be field-adjusted to water conditions.
The HumidiClean power module accepts a proportional signal and, in response, pulses power to the heating elements to provide fully modulated output. Steam output is continuously adjusted to satisfy necessary humidity requirements.
Features
 Steam production is pure, sterile and free of minerals
 No risk of bacteria with standard aquastat
 Steam production from 4.1 to 130 Kg/Hrs
 Can be worked with tap, soft, RO and DI water
 Alpha digital in standard
 Drived by microprocessor with proportional control
 Easy maintenance with the system Ionic Bed which reduced the deposit of
minerals in the tank and also on the heating elements
 Password protected programmable keypad
 Diagnostic indicating LCD display
 Continual checking diagnostic routines
 High and low water level detection
 Possibility to link Humidiclean to a computer via RS485
Options
 Blower pack for direct discharge humidification
 BACnet or LonWorks protocols
 Stainless steel manifold