Energy consumption & CO₂ emission according to humidification technologies

Date : 29 May 2026

Customer : test

Project : teds

Revision : fdgdf

Client Information


Project Location : Evreux in France

Altitude : 129.69 m

Atmospheric Pressure : 99 776 Pa

Location : Latitude : 49.027, Longitude : 1.1515

Input Data

$ CO2 Energy cost and CO2 emission

c€ /kWh electricity c€ /kWh gas gCO2 per kWh electric gCO2 per kWh gas
16c€ 9.9c€ 45gCO2eq 198gCO2eq

Application - Set points - Sensible / Latent internal loads

Application : Cold Storage

Day hour : from0 hto24 h

⚙️Set point air conditions

Condition Tdb rh x
Winter 20°C 50% 7.38g/kg
Summer 20°C 50% 7.38g/kg

🔥Internal Loads

Others sensible loads day0 kW
Others sensible loads night0 kW
Others latent loads day0 kg/h
Others latent loads night0 kg/h

👥Occupancy

N° People/h (day):0
N° People/h (night):0

Extreme Climatic Values

☀️Summer – Cooling

Tdbmax :35.43°C
Twb :21.48°C
x :10.55g/kg

❄️Winter – Heating

Tdbmin :-4.48°C
x :2.6g/kg
rh :98.9%

💧Humidification

Tdb :-2.96°C
Xmin :2.37g/kg
rh :79.3%

🌫️Dehumidification

Tdb :27.03°C
Xmax :17.24g/kg
Tdew :22.29°C

💨Evaporation

Tdb :27.03°C
Twbmax :23.59°C
x :17.24g/kg

📊Climatic Data

Data Sourcehttps://power.larc.nasa.gov.
Total Hours 8 760h
Data Year2025

External Climatic Data

External Dry bulb Temperature Variation

External Humidity Ratio Variation

AHU Data

🏢 AHU Information

AHU off period
Fan efficiency95%
Width700mm
Height700mm
Internal surface0.49m²

💨 Ventilation Data

Total air flow day2500m³/h
% Fresh air day100%
Total air flow night2500m³/h
% Fresh air night100%

🔥 AHU Heating Elements

Choice Setup (°C) Efficiency (%)
Anti frost battery No - -
Air heat recovery system No - -

Heating Hours : from 0 h to 24 h

💧 Air Humid Recovery system

Choice Efficiency
No -

Humidification Hours : from 0 h to 24 h

Humidified Air Flow : Fresh air only

Type of water isothermal humidifiers: R.O water

➤➤➤Air velocity in AHU

For steam For humidifier with contact pad
Air Velocity day 1.42 m/s 2.41 m/s
Air Velocity night 1.42 m/s 2.41 m/s

📏 EvaPack Selection

EvaPack size
Width (mm) 700mm
Height (mm) 700mm

Energy Cost and CO2 Emission

Sensible Heating

Input Data

Parameter Value
PreHeating system Electric heater
Efficiency 100%
Cost per kWh (c€) 16c€

Result

Parameter Value
Eq g CO2 per kWh 45.0gCO2eq
Actual Consumption 63MWh
Heating Cost 10 236€
CO2 emission 2.88tCO2
Max required power isothermal hum. 20.48 kW
Max required power adiabatic hum. 31.02 kW

Humidification

Annual General Humidification Information

Hour Number Total production Max production capacity Total Hum. recovery
5 319 h 30 606 kg 15 kg/h 0 kg

Monthly evolution of humidification demand

Electric Humidifier

Parameter Value
Dispersion tube Diameter 40
Required Capacity 17.02 kg/h
Distribution steam pipe length 3 m
Insulated distribution pipe No

Hygienic & controlled evaporation

Parameter Value
EvaPack configuration DW - Proportional Control
Pad thickness selection (mm) 75 mm
Type of water R.O water
Annual Estimation & Comparison for humidification
Electric Humidifier Hygienic & controlled evaporation
Annual avg. water consumption 41 843 kg 38 263 kg
Annual avg. energy consumption 28 MWh 21 MWh
Humidification Cost 4 571 € 3 449 €
CO2 emission 1.29 tCO2eq 0.97 tCO2eq
*The calculated data are estimates based on given inputs and assumptions.They are for informational purposes only and may vary with different conditions.